Gas leaks are a constant threat to factories!
6000-KN Combustible Gas Detector
6000-KN for MTI Product
Combustible
The 6000-KN combustible gas detector is designed for use with catalytic sensor , featuring 4~20mA , HART (option) or mV output (option) .
Applications-
Petrochemical / Pharmaceutical / Chemical / Manufacturing / Aerosol Filling / Steel-Making / Semiconductor etc. hazardous areas
- 4~20mA output (3-wire or 4-wire).
- HART output (option).
- mV output (option).
- CNS/CPA approved for hazardous areas use.
- CE approved for RFI/EMC protection.
- CE approved for EFT/Burst Immunity.
- Low maintenance cost and easy calibration.
Specification
Principle
Catalytic
Output signals
4~20mA , 4~20mA (HART) or mV
Operating conditions
Standard : -20~+60°C, 0~99%RH , 100%RH (non condensing), 1 atm±20%
Display range
0~100%LEL
Operating voltage
4~20mA & HART : 24VDC normal (12~32VDC)
mV : 5VDC normal
Operating current
mV : 200mA
Power consumption
< 3W
Installation
Wall or pipe mounting
Enclosure material
Transmitter : Aluminum alloy ; Sensor : S.S.316
Weight
2.16kg
Ingress protection
IP 66 with corrosion-resistant
Feature
Over-current protection
Self-test indication
Approvals
CNS : Ex d IIC T6 Gb
CPA (China)
CE : EN61000-6 -2/-4
EFT/Burst Immunity CE : EN61000-4 -4