Gas leaks are a constant threat to factories!

ITEL Gas Detector

ITEL for MTI Product

Combustible/Toxic/VOC

The ITEL multi gas detector is designed for use with gas sensor of catalytic , electrochemical , PID or NDIR sensor cartridge. ITEL have 4~20mA , Relay , HART(option) & RS-485 signal output interface.

Applications-
Petrochemical / Pharmaceutical / Chemical / Manufacturing / Aerosol Filling / Steel-Making / Semiconductor etc. hazardous areas

  • 4~20mA output (3-wire or 4-wire).
  • RS-485 (Modbus RTU) or HART output.
  • Relay output (A1,A2,Fault).
  • Calibration and adjustment use a magnetic wand.
  • Display are shown the gas name , range , reading and alarm(A1,A2,Fault).
  • UL/CNS/CPA approved for hazardous areas use.
  • CE approved for RFI/EMC protection.
  • CE approved for EFT/Burst Immunity.
  • Low maintenance cost and easy calibration.

Specification

Principle

Catalytic / Electrochemical / PID / NDIR

Output signals

Analogue : 4~20mA (3-wire or 4-wire)
Digital : RS-485 (Modbus RTU) or HART [Ver.7]
Relay : Fault/A1/A2 (30VDC & 2A)

Operating temperature

Standard : -20~+60°C
High : -40~+85°C (option)

Operating conditions

0~99%RH , 100%RH (non condensing) , 1 atm±20%

Local Display

LED : 2 rows , 4 digital characters, 20 x 7 dot-matrix display
LCD : back-lit biserial display
Tricolor LCD : back-lit biserial display (Normal : Green / Alarm : Red / Fault : yellow)

Display range

0~100%LEL / 0~100%VOL / 0~9999ppm / 0~9999mg/m3 (can be set by user)

Operating voltage

24VDC normal (18~32VDC)

Power consumption

< 6W

Installation

Wall or pipe mounting

Enclosure material

Transmitter housing : Aluminum alloy or S.S.316

Sensor housing : S.S.316

Weight

Aluminum alloy : 2.2kg ; S.S.316 : 6.5kg

Ingress protection

IP 66 with corrosion-resistant ; NEMA 4X

Feature

Adjustable alarm settings
Latching / Non-Latching alarms
Self-test indication
Simulation / Calibration 4-20mA output
Password protected

Approvals (Aluminum alloy only)

UL : Class I , Division 1 , Groups B , C & D
Class II , Division 1 , Groups E , F & G ; NEMA 4X
CPA (China)

Approvals

CNS(ITRI) : Ex d IIC T6 Gb + Ex tb IIIC T85°C Db

Test reports

EMC/RFI CE : EN61000-6 -2/-4
EN 50270
EFT/Burst Immunity CE : EN61000-4 -4