Gas leaks are a constant threat to factories!
7000 Plus Toxic Gas Detector (Aluminum)
7000 Plus for MTI Product
Toxic
The 7000 Plus Toxic gas detector is designed for use with sensor cartridge of catalytic , electrochemical , PID or NDIR type . 7000 Plus have 4~20mA , Relay , HART (option) & RS-485 signal output interface.
Applications-
Petrochemical / Pharmaceutical / Chemical / Manufacturing / Aerosol Filling / Steel- Making / Semiconductor etc. hazardous areas
- 4~20mA output (3-wire or 4-wire).
- 4~20mA output mode can select Source , Sink , Isolated.
- RS-485 (Modbus RTU) or HART output .
- Relay output (A1,A2,Fault).
- Alarm (A1,A2&Fault).
- Calibration & adjustment use a magnetic wand.
- Use MTI Smart Swappable Module.
- Up to 5 points calibration.
- Calibration Remind (180 days).
- CNS approved for hazardous areas use.
- Low maintenance cost & easy calibration.
Specification
Output signals
Analogue : 4~20mA (3-wire or 4-wire)
Digital : RS-485 (Modbus RTU) or HART [Ver.7]
Relay : Fault/A1/A2 (30VDC/5A or 250VAC/5A)
Operating temperature
-40~+85°C
Operating relative
0~95%RH (non condensing),1 atm±20%
Local Display
4 digital characters
Display range
0~9999
Operating voltage
24VDC normal (12~32VDC)
Power consumption
< 6W
Installation
Wall or pipe mounting
Enclosure material
Transmitter housing : Aluminum alloy
Sensor housing : S.S.316
Weight
2.2Kg
Ingress protection
IP66
Feature
Adjust Alarm value, Alarm latching & action method
Self-test indication
4~20mA output test & Relay test
4、8、12、16、20mA output value adjusted
Password protection
5 point calibration (Zero&Span, 2 points, 3 points, 4 points or 5 points)
Approvals
CNS : Ex db IIC T6 Gb X + Ex tb IIIC T85°C Db X
Test reports
CE-EMC/RFI : EN 50270 (2015)