Gas leaks are a constant threat to factories!

7100 Toxic Gas Detector (Loop Power)

7100 for MTI Product

Toxic
The 7100 toxic gas detector is designed for 2-wire gas detector with electrochemical sensor , featuring 4~20mA output.

Applications-
Petrochemical / Pharmaceutical / Chemical / Manufacturing / Aerosol Filling / Steel-Making / Semiconductor etc. hazardous areas

  • 4~20mA output(2-wire loop powered).
  • Calibration and adjustment use a magnetic wand.
  • CNS approved for hazardous areas use.
  • Low maintenance cost and easy calibration.
Categories: , Tags: ,

Specification

Principle

Electrochemical

Output signals

Analogue : 4~20mA

Operating conditions

-20~+60°C , 0~99%RH , 100%RH (non condensing) , 1 atm±20%

Local Display

LCD : biserial display

Display range

0~100%VOL / 0~2000ppm / 0~2000mg/m3

Operating voltage

24VDC normal (18~32VDC)

Power consumption

< 1W

Installation

Wall or pipe mounting

Enclosure material

Transmitter housing : Aluminum alloy ; Sensor housing : S.S.316

Weight

1.87kg

Ingress protection

IP 66 with corrosion-resistant

Feature

Over-current protection
Self-test indication
One-Man calibration
Control by using a magnetic wand

Approvals

CNS : Ex db IIC T5/T4 Gb